Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 203
FM Output Filter
Program Terminal Analog Output Terminals
This parameter is used to select the degree of filtering to be
applied to the FM output terminal.
The output reading provided by the FM terminal is filtered via a
rolling average. The sample time of the average is selected at
this parameter.
A longer average time results in a more stable output signal.
This parameter setting further filters the F678 setting for the FM
terminal.
See F005 for additional information on this parameter.
Note: Selecting No Filter has no effect on the setting of F678.
Settings:
0 — No Filter
1 — Filter (10 mS)
2 — Filter (15 mS)
3 — Filter (30 mS)
4 — Filter (60 mS)
5 — Filter (120 mS)
6 — Filter (250 mS)
7 — Filter (500 mS)
8 — Filter (1 S)
Direct Access Number —
F684
Parameter Type — Selection List
Factory Default — No Filter
Changeable During Run — Yes
AM Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the AM out-
put terminal.
The AM output terminal response may be set to respond
inversely (-) or directly (+) to the input signal.
See F670 for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number —
F685
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
AM Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input
signal produces a zero-level output at the AM terminal.
Set the function selected at F670 to zero and then set this
parameter to zero for proper operation.
See F670 for additional information on this parameter.
Direct Access Number —
F686
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — +100.0
Units — %
F684 – F688