100 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
V/f 5-Point Setting Voltage 1
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 1 setting establishes the output
voltage level that is to be associated with the frequency setting of
F190 (V/f 5-Point Setting Frequency 1).
The F701 parameter setting will determine if the on-screen selec-
tion for this parameter appears in the form of a Voltage (V) or as
a Percentage (%) of the ASD rating.
If using Voltage as a unit of measure and with no voltage correc-
tion (F307 Disabled), the limit of the on-screen display value for
this parameter is 200 volts for the 230-volt ASD and 400 volts for
the 460-volt ASD.
The actual output voltage is scaled to the maximum EOI display
values (e.g., a 100-volt EOI display corresponds to a 115-volt
actual output for the 230-volt ASD — ½ of the full display range).
If using % as a unit of measure and with no voltage correction
(F307 Disabled), the ASD output voltage will be the percentage
setting times 230 for the 230-volt unit (or % times 460 volts for
the 460-volt unit).
See F190 for additional information on this parameter.
Direct Access Number —
F191
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 2
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 2 sets the frequency to be
associated with the voltage setting of parameter F193 (V/f 5-Point
Setting Voltage 2).
See F190 and F191 for additional information on this parameter.
Direct Access Number —
F192
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
F191 – F193