Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 101
V/f 5-Point Setting Voltage 2
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 2 establishes the output voltage
level that is to be associated with the frequency setting of F192
(V/f 5-Point Setting
Frequency 2).
The F701 parameter setting will determine if the selection for this
parameter appears in the form of a Voltage (V) or as a Percent-
age (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this parameter.
Direct Access Number
F193
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 3
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 3 sets the frequency to be
associated with the voltage setting of parameter F195 (V/f 5-Point
Setting Voltage 3).
See F190 and F191 for additional information on this parameter.
Direct Access Number
F194
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum Maximum Freq.
(F011)
Units — Hz
V/f 5-Point Setting Voltage 3
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 3 establishes the output voltage
level that is to be associated with the frequency setting of F194
(V/f 5-Point Setting
Frequency 3).
The F701 parameter setting will determine if the selection for this
parameter appears in the form of a Voltage (V) or as a Percent-
age (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this parameter.
Direct Access Number
F195
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 4
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 4 sets the frequency to be
associated with the voltage setting of parameter F197 (V/f 5-Point
Setting Voltage 4).
See F190 and F191 for additional information on this parameter.
Direct Access Number
F196
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum Maximum Freq.
(F011)
Units — Hz
F193F197