Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
V/f 5-Point Setting Voltage 4
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 4 establishes the output voltage
level that is to be associated with the frequency setting of F196
(V/f 5-Point Setting
Frequency 4).
The F701 parameter setting will determine if the selection for this
parameter appears in the form of a Voltage (V) or as a Percent-
age (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this parameter.
Direct Access Number —
F197
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
V/f 5-Point Setting Frequency 5
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 5 sets the frequency to be
associated with the voltage setting of parameter F199 (V/f 5-Point
Setting Voltage 5).
See F190 and F191 for additional information on this parameter.
Direct Access Number —
F198
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
V/f 5-Point Setting Voltage 5
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 5 establishes the output voltage
level that is to be associated with the frequency setting of F198
(V/f 5-Point Setting
Frequency 5).
The F701 parameter setting will determine if the selection for this
parameter appears in the form of a Voltage (V) or as a Percent-
age (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this parameter.
Direct Access Number —
F199
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %