Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
PG Disconnection Detection
Program Feedback PG Settings
This parameter Enables/Disables the system’s monitoring of the
PG connection status when using encoders with line driver out-
puts.
Note: The PG Vector Feedback Board option is required to use
this feature.
Settings:
0 — Disabled
1 — Enabled (with Filter)
3 — Enabled (Detect momentary power fail)
Direct Access Number
F377
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Number of RP Terminal Input Pulses
Program Feedback PG Settings
In conjunction with parameter settings F234F237, this parame-
ter is used to scale the input pulse train speed-control signal
when using the optional Expansion IO Card Option 2.
When using the optional terminal board, the frequency com-
mand can be input via the pulse train input (RP). The input pulse
frequency is calculated to the percent base data which is then
converted to the frequency based on settings F234F237.
See the Expansion IO Card Option 2 instruction manual
(P/N 58686) for additional information on the function of this ter-
minal.
Direct Access Number
F378
Parameter Type — Numerical
Factory Default — 500
Changeable During Run — No
Minimum — 12
Maximum — 9999
Units — PLS
PID Output Dead Band
Program Feedback PG Settings
While operating in the PID mode, this parameter establishes an
ASD output threshold that must be exceeded in order to activate
the configured PID control.
Direct Access Number
F379
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
F377F380