Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 153
Virtual Linear Pump Low Start/Stop Point
Program Virtual Linear Pump Start and Stop Points
During a properly configured Virtual Linear Pump operation while
in the On Forward or On Reverse modes (F385), this parameter
establishes the lower level of the Auto Start-Stop threshold.
See F385 for additional information on this parameter.
The unit of measure for this parameter may be one of the follow-
ing types — the type is selected while running the Virtual Linear
Pump Setup Wizard.
• PSI
• GPM
• Inches of Water Column
• Feet of Water Column
• CFM
• °C
• °F
• Custom
(Custom selection allows for three character spaces to be popu-
lated from the 26 alphabet and 13 special characters)
Direct Access Number —
F388
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — F403 Setting
Maximum — F393 Setting
Units — Selectable at Wizard
Virtual Linear Pump High Start/Stop Point
Virtual Linear Pump Start and Stop Points
During a properly configured Virtual Linear Pump operation while
in the On Forward or On Reverse modes (F385), this parameter
establishes the upper level of the Auto Start-Stop threshold.
See F385 for additional information on this parameter.
The unit of measure for this parameter may be one of the follow-
ing types — the type is selected while running the Virtual Linear
Pump Setup Wizard.
• PSI
• GPM
• Inches of Water Column
• Feet of Water Column
• CFM
• °C
• °F
• *Custom
Note: *Custom selection allows for three character spaces to be
populated from the 26 alphabet and 13 special characters.
Direct Access Number —
F389
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — F403 Setting
Maximum — F393 Setting
Units — Selectable at Wizard
F388 – F390