178 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Acceleration/Deceleration Switching Frequency 1
Program Special ACC/DEC Special
This parameter sets the frequency at which the acceleration con-
trol is switched from the Accel 1 profile to the Accel 2 profile
during a multiple-acceleration profile configuration.
Direct Access Number
F505
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum Maximum Freq.
(F011)
Units — Hz
IP Address Setting Method
Direct Access Number
F576
Program Communications Ethernet Settings Parameter Type — Selection List
This parameter is used to select the method used to set the IP
address for a network device (ASD).
Selecting Manual at this parameter will require that parameters
F577F580 and parameters F582F584 be used to manually
create the IP address and Subnet Mask Data, respectively, for
the device.
Selecting BOOTP or DHCP results in the IP address being sup-
plied by the server. See F577 for additional information on set-
ting the IP address.
Settings:
0 — Manual
1 — BOOTP
2 — DHCP
Factory Default — Manual
Changeable During Run — Yes
IP Card Data 1
Program Communications Ethernet Settings
Selecting Manual at parameter F576 enables parameters F577
F580 to be used to create an IP address for the connected
device.
This parameter is used to configure the IP Data Card 1 section of
the IP address of the device.
Direct Access Number
F577
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 255
IP Card Data 2
Program Communications Ethernet Settings
This parameter operates in conjunction with parameter F577.
This parameter is used to configure the IP Data Card 2 section of
the IP address of the device.
See F577 for additional information on this parameter.
Direct Access Number
F578
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 255
IP Card Data 1
IP Card Data 2
IP Card Data 3
IP Card Data 4