EasyManua.ls Logo

Toshiba Q9+ - Page 43

Toshiba Q9+
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Startup Wizard
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 31
Settings:
0 — Manual
1 — Automatic ACC/DEC
2 — Automatic ACC only
The motor and the load must be connected prior to
selecting Automatic Accel/Decel.
If Automatic Accel/Decel is not enabled, the
Acceleration screen will appear followed by the
Deceleration screen as shown below.
5. Volts Per Hertz Control Type
(F015)
This function establishes the relationship between
the output voltage and the output frequency of the
ASD.
Settings:
0 — Constant Torque
1 — Voltage Decrease Curve
2 — Automatic Torque Boost
3 — Sensorless Vector Control (speed)
5 — V/f 5-Point Setting (open 5-point setting
window)
6 — PM Drive
7 — PG Feedback Vector Control (speed)
9 — Energy Saving
10 — Advanced Energy Saving
6. Motor Current Rating
(F406)
This parameter allows the user to input the full-load
amperage (FLA) of the motor. This value is used by
the Q9 Plus ASD to determine the Motor Overload
Protection setting for the motor and may be found
on the nameplate of the motor.
7. Motor Rated Speed
(F407)
This parameter allows the user to input the rated
speed of the motor in RPM. This value may be
found on the nameplate of the motor.
8. Command Source
(F003)
This selection establishes the source of the Run
commands (e.g., F, R, Stop, etc.).
Settings:
0 — Terminal Board
2 — EOI Keypad
3 — RS485/BACnet
4 — Communication Option Board
9. Frequency Command Source
(F004)
This selection establishes the source of the
Frequency (speed) command.
Deceleration Time (F010)
Acceleration Time (F009)
Accelerati
on Time
Decelerati
on Time

Table of Contents

Related product manuals