- 22 -
FILE NO. SVM-04004
5. REFRIGERATION CYCLE DIAGRAM
5-1. RAS-13UKHP-E3 / RAS-13UAH-E3
Evaporator
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating
Cooling
Compressor
Accumulator
Condenser
Propeller fan
Outdoor unit
Capillary tube
Æ1.0 x 900
Capillary tube
Æ1.5 x 700
PH170T2-4L2
Cooling
Heating
Mark ( ) means check points of Gas Leak.
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Heating
Packed valve
(Æ12.7)
Packed valve
(Æ6.35)
0.39 m
(Connecting pipe)
0.49 m
(Connecting pipe)
T1
P
Refrigerant
R22 : 1.00 kg.
Æ12.7
Æ6.35
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 1.84 46.0 High 20/15 7/6
Heating Overload*1 2.00 ~ 2.42 52.0 ~ 59.0 Low 27/- 24/18
Low temperature 1.50 38.0 High 20/
Standard 0.49 10.0 High 27/19 35/24
Cooling Overload 0.60 15.0 High 32/23 43/26
Low temperature 0.45 2.0 Low 21/15 21/15
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
50Hz
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 During heating overload operation, a value for the high temperature limit control operation is included.
l
l
-
-10/-10
·
·