CIRCUIT OPERATION (cont’d) 
 
Speed Reference 
An external speed reference with count 25000/100% weighting is input by serial transmission or 
analog input and subjected to rate processing and limit processing to output an SP_R signal.  The sign of 
the speed reference signal is "+" for normal rotation and "-" for reverse rotation. 
 
 
 
 
 
 
 
 
 
 
 
 
Speed 
Reference 
 
 
 
 
1. Speed references 
SP_REF1 or SP_REF2 can be used when the drive speed is to be controlled from one location only.  When 
using local and remote control or there is a need for selection between two separate inputs SP_REF_AIN1 
and SP_REF_AIN2 should be used.  To select between references, one of the digital inputs should be 
programmed as SEL_DI and the selection switch connected. 
 
SP_REF_AIN1 is used when the SEL_DI input is 0 (Open).  SP_REF_AIN2 is used when SEL_DI is 1 
(Closed).  The start commands (EXT) are also different for this application.  When SEL_DI is 0, EXT0 
should be used and when SEL_DI is 1, EXT1 should be used. 
 
2. LMT_SP_MIN 
LMT_SP_MIN is used as a minimum speed.  The drive will run at this speed anytime the start command is 
on and the speed reference is less than LMT_SP_MIN.
 
 
 
EXT=1 
Jogging (option) 
JOG_R 
SP_REF1 
SP_REF2 
25000 count/100% 
 
SP_REF_AIN1 
SP_REF_AIN2 
+ 
+ 
LMT_SP_MIN 
<RATE><LIMIT> 
CR_RATE_ACC 
CR_RATE_DEC 
CR_RATE_QSTOP 
LMT_SP_F 
LMT_SP_R 
+ 
SP_R 
 
SEL_DI=1 
+