Protective Functions 
 
The main protective functions are shown in the following table.  For other faults or more details, 
refer to the troubleshooting manual. 
 
Protective Function Table 
Heavy Fault 
Medium 
Fault 
Light 
Fault 
Item Abbreviation 
Hardware
Detection
Software 
Detection
Coast 
to stop
Decel 
stop 
Stop 
request 
Alarm
Start 
Interlock
Input main switch open   AC_MCCB    O  O         
No load connected  AC_NL    O  O         
Output main switch closed 
without signal (Welded) 
ACSW_C 
   
 
 O 
Output main switch opened 
during operation 
ACSW_F 
 O O  
 
 
Output main switch open timer ACSW_T    O    O 
Brake healthy  B_HLTY    O O    
External trip from input breaker  BLA    O  O         
Brake release fault  BR_F    O    O       
Equipment ventilation fan stop   C_FN    O      O  O   
Equipment ventilation fan stop 
timer 
C_FN_T 
 O O  
 
 
Current limit timer  CL_T    O  O         
Current limit alarm  CL_TA    O      O     
Control power supply loss  CPSF    O  O*         
CPU error  CPU_A or M  O    O*         
U or W phase feedback error  CURU or W    O  O*         
Door open  DS_T    O O*    
Encoder feedback error ENCODER_F   O O*    
Rectifier  fuse fault  FUSE_xP 
FUSE_xN 
 O O*  
 
 
Ground fault alarm  GR_A_    O      O  O   
Ground fault trip  GR_T_    O  O         
External interlock  IL    O O    
Motor cooling fan stop timer  M_FN_T    O    O       
Motor cooling fan stop  M_FN    O      O  O  O 
Motor overheat  M_OH    O  O    O  O   
Motor overheat alarm  M_OH_A    O      O  O   
Main power supply loss  MPSF    O  O*         
Main power supply loss  MPSF_MV    O  O*         
Motor temperature sensor error  MTMP_S    O      O  O   
AC over-current   OCA    O  O*         
Power Module phase over-
current 
OCD_x 
 O O*  
 
 
Power Module IGBT over-
current 
OCD_xA1 
OCD_xA4 
OCD_xB1 
OCD_xB4 
O  O*  
 
 
Power Module overheat  OH_T_x    O  O*         
Transformer over heat  OH_TR    O  O*