- 47  
DRIVE INSTALLATION DRAWINGS 
Frame 0 4160V module lifting and installation 
 
WARNINGS
Disconnect power and wait 15 
minutes to ensure capacitors are 
discharged before performing 
inspection or maintenance. 
Improper handling of the fiber 
optic cables and connectors may 
cause drive failure due to 
problems transmitting signals.
Take care not to disturb fiber 
optic cables when handling 
power module.
Use module lifting attachment 
GCI6720G055 and a lifting device 
rated 250 lbs minimum for 
removal and installation of 
modules.
Power Module Removal
1.  Disconnect and remove AC
     neutral bus. 
2.  Disconnect power cables
     ACL, P, C & N.
3.  Remove control wiring
     cover (two  "A" bolts) 
4.  Disconnect control signal
     cable and 120VAC supply
     cable from module.
5.  Free slide tray by
     removing bolt "B".
6.  Pull slide tray out until
     slides lock.
7.  Remove four "C" bolts
     which secure module to
     tray.
Power Module Installation
1.  Pull slide tray out until
     slides lock.
2.  Using module lifting
     attachment and lifter, place
     module on tray. 
3.  Secure module to tray with
     four "C" bolts.
4.  Press slide release buttons
     and slide module into
     compartment (use caution).
5.  Reinstall bolt "B" to
     secure tray in position.
6.  Reconnect control signal
     cable and 120VAC supply
     cable to module
     connectors.
7.  Reinstall control wiring
     cover and secure with two
     "A" bolts.
8.  Reconnect power cables
     ACL, P, C & N.
9.  Reinstall AC neutral bus.
10. Torque all power
     connections (5/16-18 hdwr)
     to 10-15 ft-lbs.
Power Module Removal 
(cont'd)
8.  Using module lifting
     attachment and lifter,
     lift module from tray.
A
A
B
C
C
C
C
AC NEUTRAL BUS
 PINCH AREA
USE CAUTION
 PINCH AREA
USE CAUTION
CONTROL WIRING
COVER
LIFTING ATTACHMENT
LIFT HERE
N
C
P
ACN
ACL
CONTROL SIGNAL &
120VAC CABLES
PRESS BUTTON
(INSIDE OF DRAWER)
TO SLIDE TRAY BACK
PRESS BUTTON
(INSIDE OF DRAWER)
TO SLIDE TRAY BACK
 
Frame 1 4160V drive lifting and assembly 
 
 
 
 
 ...... .....  
 
 
 
 
 ...... .....   When the service drawer is withdrawn, the power modules 
have sufficient weight to tip over the Frame 1 inverter cabinet 
if it is not firmly anchored to the mounting floor, resulting in 
severe injury or death. 
 
 ...... .....   DO NOT attempt to install or withdraw the Frame 1 power 
modules before first securely anchoring the cabinet to the 
floor. 
 
Do
PC94060P007
DANGER