- 20
Overload alarm OL_A O O
Overload (5 minutes) OL5 O O
Overload (20 minutes) OL20 O O
Over speed OSS O O*
Output frequency high OSS_F0 O O*
DC bus over-voltage
positive/negative
OV_xP
OV_xN
O O*
Panel safety switch P_SW O O
Parameter setting error PARA_ERR O O
PLL phase error PHASE_ERR O O
PLD error PLD_ERR O O*
PLL error PLL O O*
Pre-charge CTT trip PRE_CTT O O
Pre-charge CTT alarm PRE_CTT_F O O O
Rectifier failure REC_F O O*
Reverse rotation failure REV_ROT_F O O*
Rotation/start failure ROTATE_FAIL O O*
Soft stall SOFT_STL O
Speed feedback error SP_ERR O O*
Speed feedback error2 SP_ERR2 O O*
Speed reference lost SP_LOST O O O
Speed reference lost alarm SP_LOST_A O O O
Motor turning start interlock SP_SIL O
Spare input 1-4 SPA1-4 O O* O O
Spare input 1-4 timer SPA1-4_T O O* O O
System configuration error SYS_ERR O O
Communication error 1-4 TL_F1-4 O O O
Main under-voltage UV_MPSF O O
DC under-voltage start interlock UV_SIL O O O
DC under-voltage trip UVD O O
External safety switch UVS O O
Input voltage phase loss VAC_PH_LOSS O O
Output current phase loss VINV_PH_LOSS O O
(Note 1) Hardware Detection: Items for which all IGBTs are directly turned off by hardware.
Software
Detection: Items for which protective interlock operation is performed by detecting errors via software.
(Note 2) "O" marks in the interlock operation fields can be selected by parameter setting.
"*" indicates that the equipment outputs the trip signal to input main circuit breaker.
“x” indicates the phase (U,V,W).