TOSHIBA
MODEL RATED MOTOR OUTPUT OUTPUT OVERLOAD MAIN CIRCUIT CONTROL
KVA HP/KW CURRENT VOLTAGE CURRENT 3-PHASE CIRCUIT SINGLE
AMPS PHASE
*G2+2010 1 0.75/0.9 3.5 200-230V 150% FOR 200V/50Hz or NO EXTERNAL
*G2+2015 1.5 1/1.2 5 3-PHASE 120 SEC. 200-230V/60Hz CONTROL
*G2+2025 2.5 2/1.8 7
(MAX VOLTAGE
110%
VOLTAGE +/- 10%
SOURCE
*G2+2035 3.5 3/2.5 10
UNDER NO LOAD)
CONTINUOUS
FREQUENCY +/- 2Hz
REQUIRED
*G2+2055 5.5 5/4.0 16
*G2+2080 8 7.5/5.5 22
*G2+2110 11 10/7.5 30
*G2+2160 16 15/11 45
*G2+2220 22 20/15 60
*G2+2270 27 25/18 70
*G2+2330 33 30/23 90
*G2+4015 1.5 1/0.75 2.7 400-460V 400V/50Hz or
*G2+4025 2.5 2/1.5 3.5 3-PHASE 400-460V/60Hz
*G2+4035 3.5 3/2.2 5
(MAX VOLTAGE VOLTAGE +/- 10%
*G2+4055 5.5 5/3.7 8
UNDER NO LOAD) FREQUENCY +/- 2Hz
*G2+4080 8 7.5/5.5 11
*G2+4110 11 10/7.5 15 380-460V 380V/50Hz or
*G2+4160 16 15/11 22 3-PHASE 400-460V/60Hz
*G2+4220 22 20/15 30
MAX VOLTAGE
VOLTAGE +/- 10%
*G2+4270 27 25/18.5 38
UNDER NO LOAD) FREQUENCY +/- 2Hz
*G2+4330 33 30/22 45
*G2+4400 40 40/30 55
*G2+4500 50 50/37 69
*G2+4600 60 60/45 83
*G2+4750 75 75/55 104
*G2+410K 100 100/75 138
*G2+412K 125 125/90 172 130% FOR
*G2+415K 150 150/110 206 195 SEC.
*G2+420K 200 200/150 275 110%
*G2+425K 250 250/200 343 CONTINUOUS
**G2+430K 300 300/225 415
3.0 Standard Specifications
INPUT POWER (Volt/Freq)RATING
3 - 1
* These units are UL/CUL (Underwriters Laboratories Inc.) listed and CSA (Canadian Standards
Association) certified.
** Unit is UL/CUL listed only.