Table 29. Diagnostics AFD (continued)
Diagnostic
Name and
Source
Affects
Target
Severity
Persistence
Active Modes
[Inactive
Modes]
Criteria
Reset
Level
Controller
AFD
(a)
AFD Comm Loss:
Main Processor -
xA
Cprsr
Immediate NonLatch NonLatch All
TR200 Alarm Code (W17), Alarm Word:
1, Bit: 4, Dec: 16
TR200 detected communication loss to
unit controller known as Control Word
Timeout warning on TR200.
(Note: In case where the TR200 losses
communication with the unit controller, the
UC will not see this diagnositc via the
alarm word. This has been included even
though UC will most likely not see this
alarm.)
Remote
AFD Fault Mains -
xA
Cprsr
Immediate NonLatch
Momentary
NonLatch
All
TR200 Alarm Code (A36), Alarm Word:
1, Bit: 24, Dec: 16777216
Active if the supply voltage to the
adjustable frequency drive is lost.
Remote
AFD General Fault
- xA
Cprsr
Immediate
NonLatch
(b)
Varies All
This is a catch-all group for any faults in
alarm words 1 or 2 that are not listed here.
These faults are unlikely to occur. They
are treated with immediate attention since
they are not expected.
Local
(c)
AFD Ground Fault
- xA
Cprsr
Immediate Latch
Latch (Trip Lock)
All
TR200 Alarm Code (A14), Alarm Word:
1, Bit: 2, Dec: 4
There is a discharge from the output
phases to ground, either in the cable
between the adjustable frequency drive
and the motor or in the motor itself.
Local
AFD Harmonic
Filter Over
Temperature - xA
Cprsr
Immediate NonLatch
Momentary
NonLatch
All
TR200 Alarm Code (A60), Alarm Word:
2, Bit: 12, Dec: 4096 The AFD Harmonic
Filter temperature has exceeded the
maximum allowed value. This diagnostic is
also non-latching on the AFD itself. The
drive calls alarm 60 because that is tied to
I/O pins 12 and 18, which function as a
safety interlock. Note that on the TR200
drive this diagnostic will populate as [A60]
External Hardware Interlock.
Remote
AFD High
Pressure Cutout -
xA
Cprsr
Immediate Latch
Latch (Trip Lock)
All
TR200 Alarm Code (A68), Alarm Word:
1, Bit: 30, Dec: 1073741824
The respective drive’s Safe Stop circuitry
was activated (open circuit). The
respective compressor’s High Pressure
Cutout Switch is wired into this circuit, and
will cause an immediate shutdown of the
drive and compressor in the event of an
HPC trip.
Local
AFD High Torque -
xA
Cprsr
Immediate NonLatch
Momentary
NonLatch
Running
TR200 Alarm Code (A12), Alarm Word:
1, Bit: 6, Dec: 64
The torque is higher than the value in
par.4-16 Torque Limit Motor Mode.
Remote
AFD Initialized - xA
Cprsr
Immediate NonLatch
Momentary
NonLatch
All
TR200 Alarm Code (A80), Alarm Word:
1, Bit: 29, Dec: 536870912
Parameter settings are initialized to default
settings after a manual reset.
Remote
AFD Internal Fault
- xA
Cprsr
Immediate Latch
Latch (Trip Lock)
All
TR200 Alarm Code (A38), Alarm Word:
1, Bit: 17, Dec: 131072
This fault could occur from various
situations, please contact engineering.