AC-SVX001A-EN
71
Stopped to Starting
The following diagram shows the timing from a
stopped mode to energizing the first compressor. The
shortest allowable time would be under the following
conditions:
• No motor restart inhibit time left from subsequent
starts
• Evaporator Water flow occurs quickly with pump on
command
• Need to cool (differential to start) already exists
• The above conditions would allow a compressor to
start in about 20 seconds.
Figure 53. Sequence of events: stopped to starting
Confirm Presence
of Oil W ithin
90 Seconds
Auto Mode com m anded
by Front Panel or BAS
Confirm Evaporator Water Flow
(6 Second Filter)
Enforce Restart Inhibit Timer
(0 to 1 minute)
Auto
Energize Evaporator
Water Pum p Relay
Confirm Evaporator Water
Flow W ithin 20 minutes
(6 Second Filter)
Oil Heaters
Always Energized when
Compressor is De-energized
EXV remains closed
Wait for Need
To Cool
(Diff to Start)
Call for Cooling
(Differential to Start is met)
Confirm
Presence of Oil
(0 to 90 seconds)
EXV m oving to
Preposition
0 to 25 Seconds
Send Start Command
to Lead Com pressor*
Transition to
Running
Start Control of
Condenser Fan Flow
Pre-Position EXV of
Lead Circuit
Check Evap Pressure for
Low Pressure Cutout
* Lead compressor (and its lead circuit) is
determined by staging algorithm - “Fixed Staging”
or “Balanced Wear” selection - also influenced by
lockouts, restart inhibit, or diagnostics present.
SSttaarrtt--uupp aanndd SShhuuttddoowwnn