Evaporator Waterside Pressure
Drop Curves
Figure 17. Evaporator waterside pressure drop curve 2–pass
0
2.5
5
7.5
10
12.5
15
17.5
20
22.5
25
27.5
30
32.5
35
37.5
40
42.5
45
47.5
50
0 200 400 600 800 1000 1200 1400
Pressure Drop (ft. H2O)
Water Flow (GPM)
300T
275T
250T
225T
200T
185T
165T
150T
Figure 18. Evaporator waterside pressure drop curve 3–pass
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
0 100 200 300 400 500 600 700 800 900 1000
Pressure Drop (ft. H2O)
Water Flow (GPM)
300T
275T
250T
225T
200T
185T
165T
150T