AC-SVX001A-EN
75
Normal Shutdown to Stopped or Run
Inhibit
The following diagram shows the Transition from
Running through a Normal (friendly) Shutdown. The
dashed lines on the top attempt to show the final mode
if stop is selected via various inputs.
Figure 57. Sequence of events: normal shutdown to stopped or run inhibit
* Note: Operational Pumpdown is required if the Outdoor Air Tem perature is less than 50F.
**
Note: Operational Pumpdown is Terminated Normally when the Evaporator Refrigerant
Pressure is at or below 20 PSIA.
The Maximum Allowed Tim e for Operational Pumpdown is 2 Minutes.
S h u ttin g D o w n
R u n n ing C irc u it M o d e s: S h u ttin g D ow n
S ubM o d e : O p erational P um pdow n
*
O p e ra tio nal Pum pdow n
(0 S e conds to 2 M in u te s)
Fully C lo se E X V
P erfo rm O p erational
P um pdow n for A ll
R u n n ing C irc u its if
R equired
*
IF*
C lo se E X V
(0 to 2 5 S eco n d s )
C h eck for
N o rm al P u m p d o w n
Term inatio n C rite ria M et
**
N o P u m p do w n R eq u ire d
P um pdo w n
R eq uired
E vap o rato r P u m p O ff D elay
(A d ju stable 1 to 3 0 M in u tes)
S end S to p C o m m and to
A ll
R u n n ing C o m pre ssors
E nergize A ll H e a ters
Fully C lo se B o th E X V s
Turn O ff A ll R u n n in g
C irc u its C o n d e n ser F ans
D e-E n erg ize E vap o rato r
W ater P u m p R elay
S topp e d
or
R un In h ib it
O n e or
M o re
C irc u its
R un n in g
N orm a l P u m pd ow n T e rm in a tion **
C riteria is M et fo r A ll C ircu its
Lo c al Sto p
C h iller Le ve l D iag n ostic – N o rm al Shutd o w n L a tch ed
C h iller Le ve l D iag n ostic – N o rm al Shutd o w n N o n la tched
B u ilding A u tom ation S y stem S top
E xtern al Auto -S top
S h u ttin g D o w n
C irc u it M o d e s :
A uto
S top p ed o r R un In h ib it
C irc u it M o d e s :
S topp e d or A u to
*Note: Operational Pumpdown is required if the
Outdoor Air Temperature is less than 50°F.
** Note: Operational Pumpdown is terminated
normally when the Evaporator Refrigerant Pressure
is at or below 20 psia.
The Maximum Allowed time for Operational Pumpdown
is 2 minutes.
SSttaarrtt--uupp aanndd SShhuuttddoowwnn