AC-SVX001A-EN
Table 27. Diagnostics main processor (continued)
Diagnostic
Name
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
Software Error
1002: Call
Trane Service
All functions Immediate Latch All
Reported if state chart misalignment in stopped or
inactive state occurred while a compressor was seen
to be operating and this condition lasted for at least 1
minute (cmprsr operation due to Service Pumpdown
or with Contactor Interrupt Failure diagnostic is
excluded). The presence of this software error
message suggests an internal software problem has
been detected. The events that led up to this failure,
if known, should be recorded and transmitted to
Trane Controls Engineering
Local
Software Error
1003: Call
Trane Service
All functions Immediate Latch All
Reported if state chart misalignment occurred
inferred from either Capacity Control, Circuit, or
Compressor State Machines remaining in the
Stopping state for more than 3 minutes. The
presence of this software error message suggests an
internal software problem has been detected. The
events that led up to this failure, if known, should be
recorded and transmitted to Trane Controls
Engineering
Local
Starts or Hours
Modified
Cprsr1A
None Info NonLatch All
The current value for the cumulative starts and or
hours for the given compressor have been modified
by a write override from TU
NA
Starts or Hours
Modified
Cprsr2A
None Info NonLatch All
The current value for the cumulative starts and or
hours for the given compressor have been modified
by a write override from TU
NA
Suction Rfgt
Pressure
Transducer
Cprsr1A
Circuit Immediate Latch All Bad Sensor or LLID Remote
Suction Rfgt
Pressure
Transducer
Cprsr2A
Circuit Immediate Latch All Bad Sensor or LLID Remote
Unexpected
Shutdown
AFD1A
Circuit Normal Nonlatch
All Cprsr
Running
modes,
Starting,
Running and
Preparing to
Shutdown
The respective AFD status reported back that it is
stopped when the MP thinks it should be running and
no AFD shutdown diagnostic exists. This diagnostic
will be logged in the active buffer and then
automatically cleared. This diagnostic could be
caused by intermittent communication problems
from the AFD to the MP, or due to misbinding
Remote
Unexpected
Shutdown
AFD2A
Circuit Normal Nonlatch
All Cprsr
Running
modes,
Starting,
Running and
Preparing to
Shutdown
The respective AFD status reported back that it is
stopped when the MP thinks it should be running and
no AFD shutdown diagnostic exists. This diagnostic
will be logged in the active buffer and then
automatically cleared. This diagnostic could be
caused by intermittent communication problems
from the AFD to the MP, or due to misbinding
Remote
DDiiaaggnnoossttiiccss