Parameters for Danfoss frequency converter FC102
[3] Automatic energy optimiza-
tion VT
According to motor nameplate
According to motor nameplate
According to motor nameplate
According to motor nameplate
According to motor nameplate
[2] Switch off of thermistor
Connect thermistor to 50/54
According to AHU data sheet
Max[Hz]=max speed [rpm]/nominal
speed [rpm]*50[Hz]
Speed increase after start 1
Speed decrease after stop 1
According to AHU data sheet
Max[Hz]=max speed [rpm]/nominal
speed [rpm]*50[Hz]
Nominal current according to motor
nameplate
Start command clamp 12/18
Bridge 12/27 necessary for operation
Dropout of signal function
Clamp 53 minimum frequence
Clamp 53 maximum frequence
According to AHU data sheet
Max[Hz]=max speed [rpm]/nominal
speed [rpm]*50[Hz]
Connections control cables:
50=+10V, 54=analog input 2
12=+24V, 18=digital input
12=+24V, 27=digital input
Table 6: parameters for Danfoss frequency converter FC102