SO-SVN037A-EN 5
General Information
About This Manual
The step-by-step instructions outlined in this manual describe
the procedures required to successfully upgrade an older
Tracer™ CH530 DynaView equipped CVHE, CVGF, CVHF,
CVHG, CDHF, or CDHG CenTraVac™ chiller to a Symbio 800
AdaptiView display system. This manual also provides
instructions and describes the procedures required to upgrade
a CH531 prebuilt panel retrofit-equipped chiller to a Symbio
800 AdaptiView display system.
Notice that the installation instructions in this manual are
divided into the following general topic areas:
1. Check the configuration and set-points in the DynaView
display.
2. Save the DynaView display configuration and set-points.
3. Shut down power.
4. Remove the old control panel door.
5. Install new control panel door and Symbio 800 controller.
6. Choosing display arm mounting location.
7. Mount display arm and new display.
8. Install 1A2 power supply (if not already present).
9. Install 1A2 power supply on CH531 prebuilt panels.
10. Install quad relay output LLID (required if using chiller
control sequence 1).
11. Install communication cable between the 1A1 and 1A2
power supplies.
12. Connect input power wiring to the 1A2 power supply.
13. Routing new wire into and out of the control panel
enclosure.
14. Wiring connections to the Tracer AdaptiView display and
the Symbio 800 controller.
15. Before restoring system power.
16. Restoring system power.
17. Programming the Tracer AdaptiView display.
18. Full page schematic wiring diagrams.
Unit Model Number
For service purposes, Trane Model CDUB Symbio 800
AdaptiView display upgrade packages are assigned a multiple
character alphanumeric model number that precisely identifies
each unit.
An explanation of the identification code that appears on the
unit nameplate is shown below. Use of the service model
number will enable the owner/operator, installing contractors,
and service technicians to define the operation, components
and options for any specific unit.
Refer to the model number printed on the nameplate when
ordering replacement parts or requesting service.
Other Required Manuals
This manual must be used with the following publications (or
their most recent versions):
• CenTraVac™ Water-cooled Chillers Models CVHE, CVHF,
and CVHG With Symbio™ Controls - Installation,
Operation, and Maintenance (CVHE-SVX005*-EN
1
).
• CenTraVac™ Water-Cooled Chillers AdaptiView™
Display with Symbio™ Controls - User Guide (CTV-
SVU004*-EN
1
).
• Tracer® TU Service Tool For Water-Cooled CenTraVac™
Chillers with Symbio™ Controls - Programming Guide
(CTV-SVP004*-EN
1
).
• CenTraVac™ Water-cooled Chillers with
Symbio™Controls Diagnostic Descriptions,
Troubleshooting Tables, and Control Component
Overview - Diagnostics Manual (CTV-SVD005*-EN
1
).
• Tracer® TU Service Tool - User Guide - (BAS-SVU047*-
EN
1
).
• Symbio™ Panel Upgrade - Programming Guide (SO-
SVP002*-EN).
Required Tools
Normal service tools are required to perform the majority of the
work. A service technician with a well stocked tool chest should
have the right tools to perform the job.
In addition to the normal service tools and hardware, the
following is a partial list of specific field supplied hardware/
software components and special tools that are also required
to perform the display retrofit:
• An RS-232 male DB9 to female DB9 pin to pin serial cable
to connect the DynaView to a PC or laptop computer.
Note: The cable must not be a “null-modem” cable. The
cable must be less than 50 feet in length.
1
A copy of this manual is shipped with the upgrade kit.