8 AFDH-SVN004C-EN
General Information
This manual describes the procedures required to install
NEMA 1 AFDH Air-Cooled Adaptive Frequency Drive
package in place of existing direct mount starter,
Transition mount starter, and LiquiFlo 1.0/1.5 drive on
Trane CVHE, CVHF, CVHG model centrifugal chillers and
retrofit LiquiFlo1.0/1.5 drives.This only applies to chillers
with Tracer® AdaptiView™ controller.
E-Frame AFDH can be ordered in a unit-mounted
configuration. Voltage options include 380/400V, 460/
480V, and 575/600V.
The E-Frame units can be equipped with drive rating:
• 658 amps, 745 amps, 800 amps, 880 amps, or 990 amps
for 380V/400V.
• 590 amps, 678 amps, 730 amps, 780 amps, or 890 amps
for
460V/480V.
• 450 amps, 500 amps, 570 amps, 630 amps, 730 amps,
or
850 amps for 575V/600V.
Note: The
factory installed Tracer CH530 chiller controller
system will not support an AFDH Air-Cooled
Adaptive Frequency drive. The controller system
must be upgraded to Tracer® AdaptiView™ before
an AFDH upgrade package can be installed.
The AFDH series of upgrade air-cooled Adaptive
Frequency
drive packages are only intended for
installation on existing Trane chillers with CVHE, CVHF, or
CVHG model centrifugal compressors. Trane makes no
claim of suitability or performance regarding upgrade
AFDH drives on older Trane centrifugal compressor
models or on chillers made by other manufacturers.
Although there may exist successful drive retrofits to
these units, users are cautioned that Trane has not
evaluated these installations. Accordingly, Trane cannot
provide assurances regarding performance, reliability or
suitability of upgrade AFDH installations to other than
Trane model CVHE, CVHF, and CVHG compressors.
Other Literature Required Before
Ordering or Installing an AFDH
Upgrade
This manual must be used in conjunction with the
following publications:
ECTV-PRB009*-EN, Engineering Bulletin, Chiller
Upgrades Selection and Application Guideline for
Aircooled Adaptive Frequency Drive Retrofit
BAS-SVP04*-EN, TR200 Programming Guide
CVRE-SVP01*-EN, Tracer® AdaptiView™ Panel Upgrade
Programming Guide
CTV-SVP02*-EN, TracerTU Service Tool for Water-Cooled
CenTraVac Chillers with Tracer® AdaptiView™ Controls
Programming Guide
HUB Document DOC-155220: MCT 10 Installation
Instructions.docx (Danfoss VLT Motion Control Tools MCT
10 Set-up Software manual)
HUB Document DOC-179427: Creating a Project a Master
File and Configuration for AFDH D & E Frame Drive.docx
(AFDH D & E-Frame Drive Configuration Instructions
Using MCT 10 Tool).