11 2 RT-SVP04F-EN
System Testing & Troubleshooting
Compressor Relays (MCM 1) Used With: All Rooftops or Air
Handlers with DX Cooling.
Possible Values: OFF, ON
K11 OFF K12 OFF K3 OFF K4 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Reheat Pumpout Coil Relay: ON Used With: All IntelliPak units with
Dehumidification installed
Factory Preset: ON; Reheat Valve:
CLOSED (Status Only); Cool Valve:
OPEN (Status Only)
Possible Values: Coil Relay: ON,
OFF; Reheat Pumpout: OPEN,
CLOSED; Cooling Pumpout: OPEN,
CLOSED
Reheat Valve: CLOSED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Note: This parameter may be adjusted manually only when
compressors are set to OFF. Otherwise the value is set
automatically as a function of Reheat Valve position.
Dehumid Reheat Valve Position: 0% Used With: All units with
Dehumidification installed
Factory Preset: Reheat Valve: 0%;
(Cooling Valve: 100% as status
only)
Possible Values: Reheat Valve: 0,
10-90%; Cooling Pumpout: 100%,
10-90% (Status only)
Dehumid Cooling Valve Position: 100%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Used With: All Rooftops or Air
Handlers with DX Cooling.
End Of Submenu (NEXT) For Service Mode
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
Relay State = HEAT ON Used With: Air Handlers with
Chilled Water Cooling and Hydronic
Heat.
Possible Values: Relay State=
HEAT ON, COOL ON, OVERRIDE; 0-
100%
Hydro Heat/Chilled Water Output 0%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).