RT-SVP04F-EN 19
General Information
Adjustable Function Factory Preset Changed To
To adjust
Press...
Control Parameters
Default system mode Auto SETUP
Demand limit definition for cooling None SETUP
Demand limit definition for heating None SETUP
Economizer control enable type Drybulb SETUP
Exhaust enable point 25% SETUP
Morning Warmup type Full SETUP
Supply air low limit 50 deg F SETUP
Unit Control Local SETUP
Coil Frost Cutout Temp 30 deg F SETUP
Evap Temperature Limit 35 deg F SETUP
OA Flow Calibration Gain (Front) 1.0 SETUP
OA Flow Calibration Offset (Front) 0 CFM SETUP
OA Flow Calibration Gain (Back) 1.0 SETUP
OA Flow Calibration Offset (Back) 0 CFM SETUP
OA Flow Calibration Data - Altitude: 0 feet SETUP
Unit Address (Comm3/Comm4 only) 1 SETUP
Default SETPOINTs
Economizer drybulb enable SETPOINT 75 deg F SETPOINTS
Low ambient compressor lockout (Std. units) 50 deg F SETPOINTS
Low ambient compressor lockout (Low ambient units) 0 deg F SETPOINTS
Occupied zone temp SETPOINT - cooling 74 deg F SETPOINTS
Occupied zone temp SETPOINT - heating 71 deg F SETPOINTS
Space pressure - deadband .04 iwc SETPOINTS
Space pressure - SETPOINT 0.08 iwc SETPOINTS
Occ Dehumidification 60% SETPOINTS
Occ Dehumid Hysteresis Offset 5% SETPOINTS
Unocc Dehumidification 60% SETPOINTS
Unocc Dehumid Hysteresis Offset 5% SETPOINTS
Supply Air Reheat Setpoint 70 F SETPOINTS
Supply Air Reheat Deadband 4 F SETPOINTS
Maximum Reheat Valve Limit 85% SETPOINTS
Dehumid Ovrd High Zone Temp Stpt 75 F SETPOINTS
Dehumid Ovrd Low Zone Temp Stpt 68F SETPOINTS
Cond Coil Purge Interval 90 min SETPOINTS
Unoccupied zone temp - cool 85 deg F SETPOINTS
Unoccupied zone temp - heat 60 deg F SETPOINTS
Unoccupied zone temp - morn warmup 72 deg F SETPOINTS
Min OA Flow - SETPOINT w\VCM Set per unit size SETPOINTS
Min OA Flow - deadband Set per unit size SETPOINTS
Preheat actuate temp 35 deg F SETPOINTS