26 RT-SVP04F-EN
System Operating Status
RTM Supply Fan Relay:
RTM Supply Airflow Proving:
OFF
FLOW
Used With: All Units
Possible Values: Fan = ON, OFF
Airflow = FLOW, NO FLOW
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom
menu for the creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed. (if applicable)
Supply Fan IGV/VFD Cmd Opening To 30%
Active Supply Air Pressure 2.0 IWC
Used With: All units with IGV/VFD.
Active SAP only shown if SAP is
present.
Possible Values: Opening to/
Closing to: 0-100%; Active Supply
Air Pressure= 0.0 -7.9 IWC
1. Press the NEXT key until the following screen is displayed.
OR
Active Supply Air Pressure 2.0 IWC
Used With: Rooftop units and Air
Handlers when IGV/VFD is not
installed and valid SAP sensor is
present.
1. Press the NEXT key until the following screen is displayed. Possible Values: 0.0 IWC - 7.9
IWC
Exhaust Fan OFF Used With: All units when Power
Exhaust without Statitrac is installed
without Return Fan
Possible Values: Fan= ON/OFF,
1. Press the NEXT key until the following screen is displayed.
OR
Exhaust Fan ON
Exhaust Damper/VFD
Space Pressure
Opening to
0.00 IWC
32 %
Used With: All units when Power
Exhaust with Statitrac is installed
without Return Fan
Possible Values: Fan= ON, OFF,
Damper/VFD = 0 to 100%
1. Press the NEXT key until the following screen is displayed. (if
applicable)
Note: "Exhaust Fan" and "Exhaust Damper/VFD" is shown only if
"Power Exhaust Config" is not = NONE
"Exhaust Fan" is not shown if Return Fan is installed
"Space Pressure" is shown only if Power Exhaust or Return
Fan with Statitrac is installed