RT-SVP04F-EN 27
System Operating Status
Electric Heat: ENABLED
Stage: 6 K11: ON K12: ON K1: ON
Used With: All units with Electric
Heat installed.
Possible Values: Electric Heat:
ENABLED, DISABLED By Setup,
LIMITED By Demand Limit
Stage: 0,1,2,3,4,5,6
K*: ON, OFF
1. Press the NEXT key until the following screen is displayed.
(If applicable)
Note: Enabled indicates OK to
heat; disabled indicates
NOT OK to heat, such as
during cooling.
OR
Gas Heat: ENABLED
Stage: 2 K11: ON K12: ON K1: ON
Used With: All units with Staged
Gas Heat Installed.
Possible Values: ENABLED,
DISABLED By Setup, LIMITED By
Demand Limit
Stage: 0,1,2
K*: ON, OFF
1. Press the NEXT key until the following screen is displayed. (If
applicable)
OR
Hydronic Heat ENABLED
Valve Position: Opening To: 100%
Used With: All units with hydronic
heat is installed
1. Press the NEXT key until the following screen is displayed. Low temp
air may be OK or tripped (If applicable)
Possible Values: ENABLED,
DISABLED By Setup, LIMITED By
Demand Limit, LIMITED By Low Air
Temp; Valve Position: Opening to/
Closing to 0-100%
OR
Mod Gas Heat ENABLED
Valve Position: Opening To: 100%
Used With: All units with
modulating gas heat is installed
1. Press the NEXT key until the following screen is displayed. (If
applicable)
Possible Values: ENABLED,
DISABLED By Setup, LIMITED By
Demand Limit; Valve Position:
Opening to/Closing to 0-100%
Chilled Water:
Valve Position:
Opening To
ENABLED
100%
Used With: Air Handler Units with
Chilled Water Installed
Possible Values: Chilled Water:
ENABLED, DISABLED By SETUP,
LIMITED By Demand Limit, LIMITED
By Low Air Temp; Valve Position -
Field One: Opening To, Closing To -
Field Two: 0-100%