34 RT-SVP04F-EN
System Operating Status
Cond Sump Water Level Max Input: OPEN Used With: All IntelliPak II units
with water-cooled condensers
installed.
Possible Values: Max Input:
CLOSED, OPEN; Min Input: CLOSED,
OPEN
Cond Sump Water Level Min Input: CLOSED
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
External Sump Drain Request: INACTIVE Used With: All IntelliPak II units
with water-cooled condensers
installed.
Possible Values: ACTIVE,
INACTIVE
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Reheat Coil Pumpout Relay: OFF Used With: All IntelliPak units with
Dehumidification installed.
Possible Values: Coil Pumpout
Relay: ON, OFF; Coil Pumpout Valve:
CLOSED, OPEN
Reheat Coil Pumpout Valve: CLOSED
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Dehumid Reheat Valve Position: 0% Used With: All IntelliPak units with
Dehumidification installed.
Possible Values: Reheat Valve: 0-
Max Reheat Valve Position Setpoint;
Cooling Valve: 10-100%
Dehumid Cooling Valve Position: 100%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Outside Air Temperature 70.0ºF Used With: All Rooftops or Air
Handlers with DX Cooling.
Possible Values: Active Outside Air
Temp= -40 to 200.0ºF; Low Ambient
Comp Lockout Temp= -20 to 80ºF
(Default: 50 ºF Standard, 0 ºF Low-
ambient with Hot Gas Bypass, 10 ºF
Low-ambient without Hot Gas
Bypass)
Low Ambient Comp Lockout Temp: 50ºF
1. Press the NEXT key until the following screen is displayed.