82 RT-SVP04F-EN
System Programming SETUP
Actuator Setup Return Fan VFD Used With: All units with Return
Fan installed.
Factory Presets: 0.0 VDC
Possible Values:
0.0 - 9.9 (Default
0.0)
Min Voltage 0.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Actuator Setup Return Fan VFD Used With: All units with Return
Fan installed.
Factory Presets: 10.0 VDC
Possible Values: 0.0 - 10.0
(Default 10.0)
Max Voltage 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Actuator Setup Return Fan VFD Used With: All units with Return
Fan installed.
Factory Presets: Direct Acting
Possible Values: Direct, Reverse
Direct/Reverse Act DIRECT ACTING
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Actuator Setup Exhaust Damper/VFD Used With: All Units when IGV/VFD
is installed or Return Fan is installed
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds
Max Stroke Time 60 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Exhaust Damper/VFD Used With: All Units when Power
Exhaust with Statitrac is installed or
Return Fan is installed.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts
DC
Min Voltage 2.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: For VFD, set to 0.0 VDC; for
damper, set to 2.0 VDC