RT-SVP04F-EN 83
System Programming SETUP
Actuator Setup Exhaust Damper/VFD Used With: All Units when Power
Exhaust with Statitrac is installed or
Return Fan is installed.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts
DC
Max Voltage 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Exhaust Damper/VFD Used With: All Units when Power
Exhaust with Statitrac is installed or
Return Fan is installed.
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
Direct/Reverse Act DIRECT ACTING
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Hydronic Used With: All Units when Hydronic
Heat and/or Chilled Water is
installed
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds
Max Stroke Time 60 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Hydronic Used With: All Units when Hydronic
Heat and/or Chilled Water is
installed
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 10.0 Volts
DC
Min Voltage 2.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Hydronic Used With: All Units when Hydronic
Heat and/or Chilled Water is
installed
Factory Presets: 0.0 VDC
Possible Values: 0.0 to 9.9 Volts
DC
Max Voltage 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Hydronic Used With: All Units when Hydronic
Heat and/or Chilled Water is
installed with air-cooled condensers
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
Direct/Reverse Act DIRECT ACTING
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Only one of the following two screens will be shown