System Programming SETUP
Actuator Setup Num 1 Low Ambient Used With: All Rooftop Units and
Air Handlers when DX Cooling is
installed with air-cooled condensers.
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds
Max Stroke Time 60 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Cond Fan VFD Ckt 1 Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: 60 seconds
Possible Values: 1-255 seconds
Max Stroke Time 60 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Only one of the following two screens will be shown
Actuator Setup Num 1 Low Ambient Used With: All Rooftop Units and
Air Handlers when DX Cooling is
installed with air-cooled condensers.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts
DC
Min Voltage 2.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Cond Fan VFD Ckt 1 Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: 0.0 VDC
Possible Values: 0.0 - 10.0 VDC
Min Voltage 0.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Only one of the following two screens will be shown
Actuator Setup Num 1 Low Ambient Used With: All Rooftop Units and
Air Handlers when DX Cooling is
installed with air-cooled condensers.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts
DC
Max Voltage 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Cond Fan VFD Ckt 1 Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: 10.0 VDC
Possible Values: 0.0 - 10.0 VDC
Max Voltage 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Only one of the following two screens will be shown