System Programming SETUP
Actuator Setup Num 2 Low Ambient Used With: All Units with Air-
Cooled Condensers installed
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts
DC
Max Voltage 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Cond Fan VFD Ckt 2 Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: 10.0 VDC
Possible Values: 0.0 - 10.0 VDC
Max Voltage 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Only one of the following two screens will be shown
Actuator Setup Num 2 Low Ambient Used With: All Units with Air-
Cooled Condensers installed
Factory Presets: Direct Acting
Possible Values: Direct Acting,
Reverse Acting
Direct/Reverse Act DIRECT ACTING
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Cond Fan VFD Ckt 2 Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE
Direct/Reverse Act DIRECT ACTING
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Modulating Gas Heat Used With: All Rooftop Units and
Air Handlers when Modulating Gas is
installed
Factory Presets: 90 Seconds
Possible Values: 1 - 255 Seconds
Max Stroke Time 90 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Modulating Gas Heat Used With: All Rooftop Units and
Air Handlers when Modulating Gas is
installed
Factory Presets: 2 VDC
Possible Values: 0.0 to 9.9 Volts
DC
Min Voltage 2.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.