RT-SVP04F-EN 87
System Programming SETUP
Actuator Setup Modulating Gas Heat Used With: All Rooftop Units and
Air Handlers when Modulating Gas is
installed
Factory Presets: 10 VDC
Possible Values: 0.1 to 10.0 Volts
VDC
Max Voltage 10 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Modulating Gas Heat Used With: All Rooftop Units and
Air Handlers Modulating Gas is
installed
Factory Presets: Direct Acting
Possible Values: Direct Acting,
Reverse Acting
Direct/Reverse Act DIRECT ACTING
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Exh Bypass Damper Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 60 seconds
Possible Values: 1-255 seconds
Max Stroke Time 60 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Exh Bypass Damper Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 2.0.0 VDC
Possible Values: 0.0 - 10.0 VDC
Min Voltage 2.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Exh Bypass Damper Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 10.0.0 VDC
Possible Values: 0.0 - 10.0 VDC
Max Voltage 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup Exh Bypass Damper Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE
Direct/Reverse Act DIRECT ACTING
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup OA Bypass Damper Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 60 seconds
Possible Values: 1-255 seconds
Max Stroke Time 60 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.