EasyManua.ls Logo

Trane PIC - Page 9

Trane PIC
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
9BAS-SVX08D-E4
Power supply recommendations
Power
requirements
24 VAC/VDC +6V / -12V
50 or 60 Hz
0.5 A maximum
Protection
The PIC device must receive power from a dedicated circuit which is
connected to a dedicated isolation screened transformer. The circuit
must be protected by a 0.5 A / 250V / Medium time lag circuit
breaker/fuse located next to it.
Recommended
wire
The AC/DC-power wiring requires three-wire cable.
The recommended wire is 1.5mm² (16 AWG) copper wire.
Standards
The AC/DC-power wiring complies with IEC or EN 60364-4-41 and
2006/95/EEC for electrical safety.
For compliance with 2006/108/EEC and 89/336/EEC European directive
for electromagnetic compatibility:
- EN 55022 level B
- EN 61000-3-2
- EN 61000-4-2
- EN 61000-4-4
Ground
Connection
The ground connection of the PIC (GND connector) MUST BE
connected to the building earth to prevent electromagnetic
compatibility risks.

Table of Contents