Operation
31BAS-SVX08D-E4
00001 0 1 = stop the circuit 1 bit
00002 1 1 = stop the circuit 2 bit
00003 2 1 = validation of the EVP leaving water setpoint bit
00004 3 1 = unit runs in heating mode bit
00005 4 1 = validation of the running mode bit
00006 5 1 = validation of remote controls bit
00007 6 1 = low noise is valided bit
00008 7 1 = validation of the low noise mode bit
40001 0 EVP water setpoint Temperature
Bit 7 = validation of remote control
Bit 4 = validation of the running mode
Bit 3 = running mode (0=cool;1=heat)
Bit 2 = validation of the EVP leaving water setpoint
Bit 1 = stop the circuit 2
Bit 0 = stop the circuit 1 bitfield
Bit 3 = validation of EVP water pump control
Bit 2 = EVP water pump command (0=stop;1=start)
Bit 1 = Validation of the low noise mode
Bit 0 = Low noise is validated bitfield
10001 0 1 = module I/O1 communication fault bit
10002 1 1 = module I/O2 communication fault bit
10003 2 1 = module I/O3 communication fault bit
10004 3 1 = module I/O4 communication fault bit
10005 4 1 = active remote water setpoint bit
10006 5 1 = unit in heating mode bit
10007 6 1 = compressor A1 runs bit
10008 7 1 = compressor B1 runs bit
10009 8 1 = liquid valve of circuit 1 open bit
10010 9 1 = EVP water pump runs bit
10011 10 1 = EVP resistor is stopped bit
10012 11 1 = default relay of circuit 1 is ON bit
10013 12 1 = compressor A2 runs bit
10014 13 1 = compressor B2 runs bit
10015 14 1 = liquid valve of circuit 2 opened bit
10016 15 1 = bypass/reverse cycle of circuit 2 runs bit
10017 16 1 = default relay of circuit 2 is ON bit
10018 17 1 = line fan 1 runs bit
10019 18 1 = Y fan 1 runs bit
10020 19 1 = delta fan 1 runs bit)
10021 20 1 = fan 2 runs bit
10022 21 1 = fans 3 and 4 run bit
10023 22 1 = warning exits bit
10024 23 1 = unit or circuit 1 manual reset fault bit
10025 24 1 = unit or circuit 2 manual reset fault bit
Table 13 - Data Point List for CGAH/CXAH/CGCL/CCUH/CGWH/RAUL chillers, SMM controller
Data
Type
Binary
Outputs
5/15
Analog
Outputs
6/16
40002 1
40003 2
Binary
Inputs
2
Offset Point Description
Unit
Function
Modbus
Index

Table of Contents