EasyManua.ls Logo

Trane TR170 - Fuses and Circuit Breakers

Trane TR170
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.2.3 Fuses and Circuit Breakers
Branch circuit protection
To prevent
re
hazards, protect the branch circuits in an installation - switch gear, machines, and so on - against short
circuits and overcurrent. Follow national and local regulations.
Overcurrent protection
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be
carried out according to local and national regulations. Circuit breakers and fuses must be designed for protection in a
circuit capable of supplying a maximum of 100000 A
rms
(symmetrical), 480 V maximum.
UL/Non-UL compliance
To ensure compliance with UL or IEC 61800-5-1, use the circuit breakers or fuses listed in Table 3.5.
Circuit breakers must be designed for protection in a circuit capable of supplying a maximum of 10000 A
rms
(symmetrical),
480 V maximum.
NOTICE
In the event of malfunction, failure to follow the protection recommendation may result in damage to the frequency
converter.
Circuit break
er Fuse
UL Non-UL UL Non-UL
Bussmann Bussmann Bussmann Bussmann Max fuse
Power [kW (hp)] Type RK5 Type RK1 Type J Type T Type G
3x200–240 V IP20
0.25 (0.33)
––
FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.37 (0.5) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.75 (1.0) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
1.5 (2.0) FRS-R-10 KTN-R10 JKS-10 JJN-10 10
2.2 (3.0) FRS-R-15 KTN-R15 JKS-15 JJN-15 16
3.7 (5.0) FRS-R-25 KTN-R25 JKS-25 JJN-25 25
5.5 (7.5) FRS-R-50 KTN-R50 JKS-50 JJN-50 50
7.5 (10) FRS-R-50 KTN-R50 JKS-50 JJN-50 50
11 (15) FRS-R-80 KTN-R80 JKS-80 JJN-80 65
15 (20)
Cutler-Hammer
EGE3100FFG
Moeller NZMB1-
A125
FRS-R-100 KTN-R100 JKS-100 JJN-100 125
18.5 (25) FRS-R-100 KTN-R100 JKS-100 JJN-100 125
22 (30)
Cutler-Hammer
JGE3150FFG
Moeller NZMB1-
A160
FRS-R-150 KTN-R150 JKS-150 JJN-150 160
30 (40) FRS-R-150 KTN-R150 JKS-150 JJN-150 160
37 (50)
Cutler-Hammer
JGE3200FFG
Moeller NZMB1-
A200
FRS-R-200 KTN-R200 JKS-200 JJN-200 200
45 (60) FRS-R-200 KTN-R200 JKS-200 JJN-200 200
3x380–480 V IP20
0.37 (0.5)
––
FRS-R-10 KTS-R10 JKS-10 JJS-10 10
0.75 (1.0) FRS-R-10 KTS-R10 JKS-10 JJS-10 10
1.5 (2.0) FRS-R-10 KTS-R10 JKS-10 JJS-10 10
2.2 (3.0) FRS-R-15 KTS-R15 JKS-15 JJS-15 16
3.0 (4.0) FRS-R-15 KTS-R15 JKS-15 JJS-15 16
4.0 (5.0) FRS-R-15 KTS-R15 JKS-15 JJS-15 16
5.5 (7.5) FRS-R-25 KTS-R25 JKS-25 JJS-25 25
7.5 (10) FRS-R-25 KTS-R25 JKS-25 JJS-25 25
11 (15) FRS-R-50 KTS-R50 JKS-50 JJS-50 50
15 (20) FRS-R-50 KTS-R50 JKS-50 JJS-50 50
18.5 (25) FRS-R-80 KTS-R80 JKS-80 JJS-80 65
22 (30) FRS-R-80 KTS-R80 JKS-80 JJS-80 65
30 (40)
Cutler-Hammer
EGE3125FFG
Moeller NZMB1-
A125
FRS-R-125 KTS-R125 JKS-R125 JJS-R125 80
37 (50) FRS-R-125 KTS-R125 JKS-R125 JJS-R125 100
45 (60) FRS-R-125 KTS-R125 JKS-R125 JJS-R125 125
Installation TR150 and TR170 Quick Guide
BAS-SVX58D-EN
08/2020 All rights reserved.
13