6.1.3 3x525–600 V AC
Frequency converter TR150 TR170
P2K2 P3K0 P3K7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90
K
P1K5
Typical shaft output
[kW]
2.2 3.0 3.7 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37 45.0 55.0 75.0 90.0 1.5
Typical shaft output
[hp]
3.0 4.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0 70.0 100.0 125.
0
2.0
Protection rating IP20 H9 H9 H9 H9 H9 H10 H10 H6 H6 H6 H7 H7 H7 H8 H8 H9
Maximum cable size
in terminals (mains,
motor)
[mm
2
(AWG)]
4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 10 (8) 10 (8) 35 (2) 35 (2)
35
(2)
50
(1)
50
(1)
50
(1)
95 (0)
120
(4/0)
4 (10)
Output current - 40
°
C (104
°
F) ambient temperature
Continuous (3x525–
550 V) [A]
4.1 5.2 6.4 9.5 11.5 19.0 23.0 28.0 36.0 43.0 54.0 65.0 87.0 105.0 137.
0
2.9
Intermittent (3x525–
550 V) [A]
4.5 5.7 7.0 10.5 12.7 20.9 25.3 30.8 39.6 47.3 59.4 71.5 95.7 115.5 150.
7
3.2
Continuous (3x551–
600 V) [A]
3.9 4.9 6.1 9.0 11.0 18.0 22.0 27.0 34.0 41.0 52.0 62.0 83.0 100.0 131.
0
2.7
Intermittent (3x551–
600 V) [A]
4.3 5.4 6.7 9.9 12.1 19.8 24.2 29.7 37.4 45.1 57.2 68.2 91.3 110.0 144.
1
3.0
Maximum input current
Continuous (3x525–
550 V) [A]
3.7 5.1 5.0 8.7 11.9 16.5 22.5 27.0 33.1 45.1 54.7 66.5 81.3 109.0 130.
9
2.6
Intermittent (3x525–
550 V) [A]
4.1 5.6 6.5 9.6 13.1 18.2 24.8 29.7 36.4 49.6 60.1 73.1 89.4 119.9 143.
9
2.9
Continuous (3x551–
600 V) [A]
3.5 4.8 5.6 8.3 11.4 15.7 21.4 25.7 31.5 42.9 52.0 63.3 77.4 103.8 124.
5
2.4
Intermittent (3x551–
600 V) [A]
3.9 5.3 6.2 9.2 12.5 17.3 23.6 28.3 34.6 47.2 57.2 69.6 85.1 114.2 137.
0
2.6
Maximum mains fuses See chapter 3.2.3 Fuses and Circuit Breakers.
Estimated power loss
[W], best case/
typical
1)
65 90 110 132 180 216 294 385 458 542 597 727 1092 1380 1658 63
Weight enclosure
protection rating IP54
[kg (lb)]
6.6
(14.6)
6.6
(14.6)
6.6
(14.6)
6.6
(14.6)
6.6
(14.6)
11.5
(25.3)
11.5
(25.3)
24.5
(54)
24.5
(54)
24.5
(54)
36.0
(79.3)
36.0
(79.3)
36.0
(79.3)
51.0
(112.
4)
51.0
(112.
4)
6.6
(14.6)
Eciency [%],
best case/typical
2)
97.9 97 97.9 98.1 98.1 98.4 98.4 98.4 98.4 98.5 98.5 98.7 98.5 98.5 98.5 96.0
Output current - 50
°
C (122
°
F) ambient temperature 70
°
C
(158
°
F)
Continuous (3x525–
550 V) [A]
2.9 3.6 4.5 6.7 8.1 13.3 16.1 19.6 25.2 30.1 37.8 45.5 60.9 73.5 95.9 2.9
Intermittent (3x525–
550 V) [A]
3.2 4.0 4.9 7.4 8.9 14.6 17.7 21.6 27.7 33.1 41.6 50.0 67.0 80.9 105.
5
3.2
Continuous (3x551–
600 V) [A]
2.7 3.4 4.3 6.3 7.7 12.6 15.4 18.9 23.8 28.7 36.4 43.3 58.1 70.0 91.7 2.7
Intermittent (3x551–
600 V) [A]
3.0 3.7 4.7 6.9 8.5 13.9 16.9 20.8 26.2 31.6 40.0 47.7 63.9 77.0 100.
9
3.0
Table 6.5 3x525–600 V AC, 2.2–90 kW (3–125 hp), Enclosure Sizes H6–H10
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. Keypad and typical control card power consumptions are included.
2) Eciency measured at nominal current. For energy eciency class, see chapter 6.4.10 Ambient Conditions.
Specications
42