6.2 EMC Emission Test Results
6.2.1 EMC Emission Test Results
The following test results have been obtained using a system with a frequency converter, a shielded control cable, a control
box with potentiometer, and a shielded motor cable.
RFI Filter
Type
Conduct emission. Maximum shielded cable length [m(ft)] Radiated emission
Industrial environment
Housing, trades and
light industries
Industrial environment
Housing, trades and
light industries
EN 55011 Class A Group 2 Class A Group 1 Class B Class A Group 1 Class B
EN/IEC
61800-3
Category C3
Second environment
Industrial
Category C2
First environment
Home and oce
Category C1
First environment
Home and oce
Category C2
First environment
Home and oce
Category C1
First environment
Home and oce
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
H4 RFI lter (EN55011 A1, EN/IEC61800-3 C2)
0.25–11 kW
(0.33–15
HP)
3x200–240
V IP20
25 (82) 50 (164) 20 (66) Yes Yes No
0.37–22 kW
(0.5-30 HP)
3x380–480
V IP20
25 (82) 50 (164) 20 (66) Yes Yes No
H2 RFI lter H2 RFI lter (EN 55011 A2, EN/IEC 61800-3 C3)
15–45 kW
(20-60 HP)
3x200–240
V IP20
25 (82) No No
30–90 kW
3x380–480
V IP20
25 (82) No No
H3 RFI lter (EN55011 A1, EN/IEC 61800-3 C1)
15–45 kW
(20-60 HP)
3x200–240
V IP20
50 (164) 20 (66) Yes No
30–90 kW
(40-125 HP)
3x380–480
V IP20
50 (164) 20 (66) Yes No
Table 6.6 EMC Test Results