6.2 EMC Emission Test Results
6.2.1 EMC Emission Test Results
The following test results have been obtained using a system with a frequency converter, a shielded control cable, a control
box with potentiometer, and a shielded motor cable.
RFI Filter
Type
Conduct emission. Maximum shielded cable length [m(ft)] Radiated emission
Industrial environment
Housing, trades and
light industries
Industrial environment
Housing, trades and
light industries
EN 55011 Class A Group 2 Class A Group 1 Class B Class A Group 1 Class B
EN/IEC
61800-3
Category C3
Second environment
Industrial
Category C2
First environment
Home and oce
Category C1
First environment
Home and oce
Category C2
First environment
Home and oce
Category C1
First environment
Home and oce
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
Without
external
lter
With
external
lter
H4 RFI lter (EN55011 A1, EN/IEC61800-3 C2)
0.25–11 kW
(0.33–15
HP)
3x200–240
V IP20
– – 25 (82) 50 (164) – 20 (66) Yes Yes – No
0.37–22 kW
(0.5-30 HP)
3x380–480
V IP20
– – 25 (82) 50 (164) – 20 (66) Yes Yes – No
H2 RFI lter H2 RFI lter (EN 55011 A2, EN/IEC 61800-3 C3)
15–45 kW
(20-60 HP)
3x200–240
V IP20
25 (82) – – – – – No – No –
30–90 kW
3x380–480
V IP20
25 (82) – – – – – No – No –
H3 RFI lter (EN55011 A1, EN/IEC 61800-3 C1)
15–45 kW
(20-60 HP)
3x200–240
V IP20
– – 50 (164) – 20 (66) – Yes – No –
30–90 kW
(40-125 HP)
3x380–480
V IP20
– – 50 (164) – 20 (66) – Yes – No –
Table 6.6 EMC Test Results
Specications
TR150 and TR170 Quick Guide
BAS-SVX58D-EN
08/2020 All rights reserved.
43
6