3.1.2 Frequency Converter Dimensions
Enclosure Power [kW (hp)]
Height
[mm (in)]
Width
[mm (in)]
Depth
[mm
(in)]
Mounting hole
[mm (in)]
Maxi-
mum
weight
Size
IP
class
3x
200–240 V
3x
380–480 V
3x
525–600 V
A
A
1)
aBbCde fkg (lb)
TR150
H1 IP20
0.25–1.5
(0.33–2.0)
0.37–1.5
(0.5–2.0)
– 195 (7.7) 273 (10.7)
183
(7.2)
75
(3.0)
56
(2.2)
168
(6.6)
9
(0.35)
4.5
(0.18)
5.3
(0.21)
2.1 (4.6)
H2 IP20 2.2 (3.0) 2.2–4.0 (3.0–5.0) – 227 (8.9) 303 (11.9)
212
(8.3)
90
(3.5)
65
(2.6)
190
(7.5)
11
(0.43)
5.5
(0.22)
7.4
(0.29)
3.4 (7.5)
H3 IP20 3.7 (5.0) 5.5–7.5 (7.5–10) – 255 (10.0) 329 (13.0)
240
(9.4)
100
(3.9)
74
(2.9)
206
(8.1)
11
(0.43)
5.5
(0.22)
8.1
(0.32)
4.5 (9.9)
H4 IP20
5.5–7.5
(7.5–10)
11–15 (15–20) – 296 (11.7) 359 (14.1)
275
(10.8)
135
(5.3)
105
(4.1)
241
(9.5)
12.6
(0.50)
7
(0.28)
8.4
(0.33)
7.9 (17.4)
H5 IP20 11 (15) 18.5–22 (25–30) – 334 (13.1) 402 (15.8)
314
(12.4)
150
(5.9)
120
(4.7)
255
(10)
12.6
(0.50)
7
(0.28)
8.5
(0.33)
9.5 (20.9)
H6 IP20
15–18.5
(20–25)
30–45 (40–60)
18.5–30
(25–40)
518 (20.4)
595 (23.4)/635
(25)
(45 kW)
495
(19.5)
239
(9
.4
)
200
(7.9)
242
(9.5)
–
8.5
(0.33)
15
(0.6)
24.5 (54)
H7 IP20
22–30
(30–40)
55–75 (70–100)
37–55
(50–70)
550 (21.7)
630 (24.8)/690
(27.2)
(75 kW)
521
(20.5)
313
(12.3)
270
(10.6)
335
(13.2)
–
8.5
(0.33)
17
(0.67)
36 (79)
H8 IP20
37–45
(50–60)
90 (125)
75–90
(100–125)
660 (26) 800 (31.5)
631
(24.8)
375
(14.8)
330
(13)
335
(13.2)
–
8.5
(0.33)
17
(0.67)
51 (112)
H9 IP20 – –
2.2–7.5
(3.0–10)
269 (10.6) 374 (14.7)
257
(10.1)
130
(5.1)
110
(4.3)
205
(8)
11
(0.43)
5.5
(0.22)
9
(0.35)
6.6 (14.6)
H10 IP20 – –
11–15
(15–20)
399 (15.7) 419 (16.5)
380
(15)
165
(6.5)
140
(5.5)
248
(9.8)
12
(0.47)
6.8
(0.27)
7.5
(0.30)
12 (26.5)
TR170
H2 IP20 2.2 (3) 2.2–4.0 (3–5) – 227 (8.9) 303 (11.9)
212
(8.3)
90
(3.5)
65
(2
.6)
19
0
(7.5)
11
(0.43)
5.5
(0.22)
7.4
(0.29)
3.4 (7.5)
H9 IP20 – –
1.5–7.5
(2–10)
269 (10.6) 374 (14.7)
257
(10.1)
130
(5.1)
110
(4.3)
205
(8.0)
11
(0.43)
5.5
(0.22)
9
(0.35)
6.6 (14.6)
1) Including decoupling plate
The dimensions are only for the physical units.
NOTICE
When installing in an application, allow space above and below the units for cooling. The amount of space for free air
passage is listed in Table 3.1.
Table 3.2 Dimensions
Installation TR150 and TR170 Quick Guide
BAS-SVX58D-EN
08/2020 All rights reserved.
7