Parameter Range Default Usage
Parameter 30-23 Locked Rotor
Detection Time [s]
0.05–1.00 s 0.10 s
Table 4.5 Set-up Wizard for Closed-loop Applications
Motor set-up
The motor set-up wizard guides users through the needed motor parameters.
Parameter Range Default Usage
Parameter 0-03 Regional
Settings
[0] International
[1] US
0–
Parameter 0-06 GridType [0]–[132] see Table 4.4. Size related Select the operating mode for restart after reconnection of
the frequency converter to mains voltage after power-
down.
Programming
30
08/2020 All rights reserved.
BAS-SVX58D-EN
4
4