Sequence of operation
CNT-SVX04A-EN
45
The external setpoint (when present) is exposed on the zone sensors front
cover.
When the hardwired setpoint adjustment is used to determine the setpoints, all
unit setpoints are calculated based on the hardwired setpoint value, the
configured setpoints, and the active mode of the controller.
Example: Assume the controller is configured with the following default
setpoints:
Absolute setpoint offset = setpoint input mean setpoint
From the default setpoints in this example, the mean of the occupied cooling
and heating setpoints is 72ºF (74 +70÷2). The absolute setpoint offset is the
difference between the setpoint input and the mean setpoint. For this example,
assume a setpoint input of 73ºF, resulting in an absolute setpoint offset of one
degree (7372=1).
The hardwired setpoint is used with the
controllers occupancy mode (occupied,
occupied standby, or unoccupied), the
heating or cooling mode, the temperature
deadband values, and the heating and
cooling setpoints (high and low limits) to
determine the controllers active setpoint.
The controller adds the absolute setpoint offset to occupied and occupied
standby default setpoints to derive the effective setpoints. The controller adds
the absolute setpoint offset to occupied and occupied standby default setpoints
to derive the effective setpoints as follows.
The ZN.520 controller determines the effective setpoint based on the following:
Hardwired setpoint input
Communicated setpoint input
Communicated setpoint offset
Default setpoints
Unoccupied cooling setpoint 85ºF
Occupied standby cooling setpoint 76ºF
Occupied cooling setpoint 74ºF
Occupied heating setpoint 70ºF
Occupied standby heating setpoint 66ºF
Unoccupied heating setpoint 60ºF
Unoccupied cooling setpoint 85ºF (same as default)
Occupied standby cooling setpoint 77ºF (default + 1 = 77)
Occupied cooling setpoint 75ºF (default + 1 = 75)
Occupied heating setpoint 71ºF (default + 1 = 71)
Occupied standby heating setpoint 67ºF (default + 1 = 67)
Unoccupied heating setpoint 60ºF