CNT-SVX04A-EN
76
Configuration
With the Rover service tool, you can calibrate two of the controllers analog
inputs: space temperature and setpoint. For each input, the calibration value is
added to the measured value to determine the effective value.
Space temperature (±10.0ºF, 0 . 1 ºF resolution)
Local setpoint (±10.0ºF, 0 . 1 ºF resolution)
Configurable parameters
Unit type
Fan coil
Blower coil
Unit ventilator
Rover service tool uses the unit type (fan coil, blower coil, or unit ventilator) to
determine and download many other aspects of the unit configuration, such as
the default analog input configuration, the default binary input configuration,
and the default binary output configuration. See Tables 43 through 54 on page
79 and Table 69 on page 102.
Cooling source
None
Hydronic (main coil changeover)
Dedicated hydronic
DX
Heating source
None
Hydronic
Dedicated hydronic
Steam
Electric heat
Hydronic (main coil changeover) + dedicated hydronic (auxiliary coil)
Hydronic (main coil changeover)