STEP 2 – Assigning the 940 Sensor to the
corresponding damper in the 950 Control.
1. From the 950 Control verify that is run-
ning software version 2.2 or later. If not,
a software upgrade is required before the
950 will recognize 940 Sensors.
2. Navigate to:
MENU > SERVICE > TECHNICIAN ACCESS >
PROCEED > ZONE SENSORS.
3. Select the corresponding damper on the
left side of the screen.
4. Select the appropriate sensor on the right
side of the screen
5. Press ASSIGN.
Repeat these steps for all communicating
sensors. See the Zone Panel literature for more
information.