18
3.6 Changing the Zone Assignment
Important: Once the 940 Sensor’s address has been selected and the sensor has been associated
to a zone in the 950 Control, changing the address at the 940 Sensor will have no effect on the zone
assignment. To change zone assignment, see below.
If the 940 Sensor’s address has been set and assigned to a zone in the 950 Control, use the following
steps to change the 940 Sensor’s assignment.
1. Change the 940 Sensor’s address.
2. On the 950 Control, navigate to:
MENU > SERVICE > TECHNICIAN ACCESS >
PROCEED > ZONE SENSORS
3. Select the appropriate zone.
4. Select the UNASSIGN button.
5. Select the new zone.
6. Select the sensor.
7. Press the ASSIGN button.
NOTE: If you need to re-enter this setup screen, press and
hold INDOOR TEMPERATURE for approximately 5 seconds.