RT-SVX34C-EN 73
Startup
at a time, when a jumper is installed across the test terminals. The unit will start the first test
step and change to the next step every 30 seconds. At the end of the test mode, control of the
unit will automatically revert to the applied "System" control method.
For Constant Volume or Variable Air Volume test steps, test modes, and step resistance values to
cycle the various components, refer to Table 28, p. 74.
Service Test Switch Location
A toggle service switch has been offered as a standard option to provide hassle free startup option
for the service person in the field. This toggle switch is located under the control panel behind the
front cover.
Table 27. Service Test Switch