RT-SVX34C-EN 9
Model Number Descriptions
P = Discharge Temperature
Sensor
R = Clogged Filter Switch
Digit 32 — Dehumidification
Option
T = Modulating Hot Gas Reheat
Model Number Notes
1. All voltages are across the line
starting only.
2. Option includes Liquid, Discharge,
Suction Valves.
3. Supply air fan drives A thru G are
used with 27½-35 ton units only and
drives H thru N are used with 40 & 50
ton units only.
4. Electric Heat KW ratings are based
upon voltage ratings of 208/240/480/
600 V. For a 240 V heater derated to
208 V, the resulting kW rating
decreases from 36 kW to 27 kW, and
from 54 kW to 41 kW. Voltage
offerings are as follows: (see Tab l e 19 ,
p. 47 for additional information):
5. The service digit for each model
number contains 32 digits; all 32
digits must be referenced.
6. Ventilation override exhaust mode is
not available for the exhaust fan with
fresh air tracking power exhaust. VOM
is available for the exhaust fan
without fresh air tracking power
exhaust.
Tons
Electric
Heater
Rated
Voltage
KW
27/36 41/54 72 90 108
27½
to 35
208 x x
240 x x
480 x x x x
600 x x x
40
and
50
208 x
240 x
480 x x x x
600 x x x x