25
Installing Vent/Combustion Air & Condensate Drain
When selecting and installing a conden-
sate pump, ensure the pump is approved
for use with condensing boilers and fur-
naces. The pump should be equipped
with an overflow switch to prevent prop-
erty damage from potential condensate
spillage.
8. The PRESTIGE Solo will typically produce
a condensate that is considered slightly
acidic with a pH content below 3.0. Install
a neutralizing filter if required by authority
having jurisdiction.
The condensate drain must remain filled
and unobstructed and allow unrestricted
flow of condensate. The condensate
should not be subject to conditions
where freezing could occur. If the con-
densate is subjected to freezing or
becomes obstructed , it can leak, result-
ing in potential water damage to the boil-
er and surrounding area.
NOTICE
CAUTION
Flexible Tubing
(or 3/4 PVC/
CPVC Piping
to Drain)
Compression
Nut with Rubber Seal
Fill Plug
with Vaccum
Break Port
Condensate
Drain Assembly
Plastic Ball
Retaining Nut
with Rubber Seal
(Hand Tight Only)
Heat Exchanger
Condensate
Drain Nipple
Fig. 14: Condensate Drain Assembly

Table of Contents

Other manuals for TriangleTube PSRKIT25

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TriangleTube PSRKIT25 and is the answer not in the manual?

TriangleTube PSRKIT25 Specifications

General IconGeneral
BrandTriangleTube
ModelPSRKIT25
CategoryBoiler
LanguageEnglish

Related product manuals