65
External Modulating Control
Factory TriMax Setting
H
EATING SETTING
F
ACTORY DEFAULT
E
Z SETUP RESET
I
NSTALLER RESET
Heating Operation Enabled
Demand Switch & Setpoint
Absolute Max CH Setpoint 194°F [90°C]
CH1 Maximum Setpoint 180°F [82°C]
CH1 Minimum Setpoint 120°F [49°C]
Reset Curve Coldest Day 0°F [-18°C]
Reset Curve Warmest Day 64°F [18°C]
CH2 Circuit Enabled
CH2 Maximum Setpoint 140°F 60°C]
CH2 Minimum Setpoint 80°F [27°C]
Warm Weather Shutdown OFF
Pump Constant Circulation Disabled
CH Post Pump Time 1 minute
Freeze Protection Enabled
Frost Protection Setpoint -22°F [-30°C]
Parallel Shift Value 0°F [0°C]
CH Call Blocking 1 minute
DOMESTIC SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
DHW Operation Enabled
Prestige Model Solo
Demand Switch
Boiler DHW Setpoint 186°F [86°C]
DHW Storage Setpoint 140°F [60°C]
DHW On Differential 6°F [3°C]
DHW Storage Adder 46°F [25°C]
System Pump During DHW Disabled
DHW Post Pump Time 1 minute
DHW Priority Timeout OFF
DHW Priority Enabled
DHW Call Blocking 0 minute
DHW to CH Call Blocking 1 minute
Antilegionella Function Disabled

Table of Contents

Other manuals for TriangleTube PSRKIT25

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TriangleTube PSRKIT25 and is the answer not in the manual?

TriangleTube PSRKIT25 Specifications

General IconGeneral
BrandTriangleTube
ModelPSRKIT25
CategoryBoiler
LanguageEnglish

Related product manuals