61
Start-Up Procedures
e. Press the LEFT and RIGHT buttons to
adjust the firing rate from 0% to 100%.
Hold down the LEFT or RIGHT but-
ton to rapidly increase or decrease the
firing rate.
f. Press the OK button while the FAN
icon is highlighted to shutdown the
burner.
g. Cycle power to the Prestige once com-
bustion testing is complete to return to
normal operation.
The combustion levels should be mea-
sured at high firing rate. If the combus-
tion levels are not within the range given
in Table 2 for the firing rate, shut the
boiler down and contact Triangle Tube
Engineering Department. Failure to
comply with this requirement could
result in severe personal injury, death or
substantial property damage.
c Measure Input - Natural Gas Only
1. Ensure the boiler is firing at maximum firing
rate. To manually place the boiler into high
fire mode, reference page 60.
2. Operate the unit for approximately 10
minutes.
3. Turn off all gas appliances within the build-
ing, except the PRESTIGE Solo.
4. At the gas meter, record the time required
to use one cubic foot of gas.
5. Calculate Natural gas input using the fol-
lowing equation:
3600 x 1000 / number of second recorded
for one cubic foot of gas = BTU/H.
6. The BTU/H calculated should approximate
the input rating listed on the unit.
WARNING
Table 3: Recommended Combustion Levels
Natural Gas
All Models
Propane
Solo 60/175/250
Propane
Solo 399
O2 Min. 2.30% 2.70% 3.70%
O2 Max. 5.30% 4.70% 5.20%
CO2 Min. 8.80% 10.70% 10.00%
CO2 Min. 10.50% 12.00% 11.00%
CO Max. 100 ppm 100 ppm 100 ppm