92 Appendix B
Integer DDC system receives
Room 1 Temperature
Anteroom Occupancy Sensor
Anteroom Door Switch
None
Room 1 Supply Air Temperature
Exhaust Pressure Flow
Exhaust Linear Flow
Exhaust Venturi
Exhaust Switch
Anteroom Key Switch
None
Positive
Negative
No Isolation
Room 1 Negative
Low Alarm Setpoint
Displayed in in. W.C.
Host DDC system must divide value by
10,000 to report pressure correctly
Room 1 Negative
High Alarm Setpoint
Displayed in in. W.C.
Host DDC system must divide value by
10,000 to report pressure correctly
Room 1 Positive
Low Alarm Setpoint
Displayed in in. W.C.
Host DDC system must divide value by
10,000 to report pressure correctly
Room 1 Positive
High Alarm Setpoint
Displayed in in. W.C.
Host DDC system must divide value by
10,000 to report pressure correctly
Room 1 Low
Temperature Alarm
Displayed in °F
Host DDC system must divide value by
10 to report temperature correctly
Room 1 High
Temperature Alarm
Displayed in °F
Host DDC system must divide value by
10 to report temperature correctly
Room 1 Negative
Mode Control
Setpoint
Displayed in in. W.C.
Host DDC system must divide value by
10,000 to report pressure correctly
Room 1 Positive
Mode Control
Setpoint
Displayed in in. W.C.
Host DDC system must divide value by
10,000 to report pressure correctly