Technical Section
21
Room1 Alarm Menu
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT VALUE
Mode of Room 1
Room Mode
The Room Mode item selects the room pressure
direction. This item enables all related alarms, for
pressure direction selected.
The PresSura Model RPC30 Controller will use the
following control parameters:
Room
Mode
Pressure
Setpoint
Exhaust
Supply
Positive
POS
SETPOINT
Maintains
room
pressure
differential
Maintains
flow and
pressure
differential
Negative
NEG
SETPOINT
Maintains
room
pressure
differential
Maintains
flow and
pressure
differential
Positive
Negative
Negative
NOTE: No Isolation Room Mode can be selected from
the main running screen.
Room 1 Alarm
Enable
Alarm Enable
The Alarm Enable item enables the low and high alarm
functions. When this item is entered, the Model RPC30
will show buttons for Low Alarms and High Alarms. Press
the button to toggle between enabling and disabling the
alarms.
NOTE: The Alarm Enable item enables or disables
pressure, flow, temperature and humidity alarms.
Enabled
Disabled
Low Alarms
Enabled
High Alarms
Disabled

Table of Contents

Other manuals for TSI Instruments PRESSURA RPC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TSI Instruments PRESSURA RPC30 and is the answer not in the manual?

TSI Instruments PRESSURA RPC30 Specifications

General IconGeneral
BrandTSI Instruments
ModelPRESSURA RPC30
CategoryController
LanguageEnglish

Related product manuals